Festo Servo drive CMMT-AS-C12-11A-P3-MP-S1

View List

Description

Festo Servo drive CMMT-AS-C12-11A-P3-MP-S1

  • Type of mounting Mounting plate, attached with screws
  • Mounting position Free convection
  • Vertical
  • Product weight 4100 g
  • Display Green/yellow/red LED
  • Operator controls Optional: CDSB operator unit
  • Conforms to standard EN 61800-3
  • EN 61800-5-1
  • EN 61800-5-2
  • EN ISO 13849-1
  • Based on standard EN 50581
  • EN 60204-1
  • EN 61508-1
  • EN 61508-2
  • EN 61508-3
  • EN 61508-4
  • EN 61508-5
  • EN 61508-6
  • EN 61508-7
  • EN 61800-2
  • EN 62061
  • Approval RCM trademark
  • German Technical Control Board (TÜV) c UL us listed (OL)
  • KC mark KC-EMV
  • CE mark (see declaration of conformity) To EU EMC Directive
  • To EC Machinery Directive
  • In accordance with EU RoHS Directive
  • CE marking (see declaration of conformity) To UK instructions for EMC
  • To UK regulations for machines
  • To UK RoHS instructions
  • Certificate issuing authority German Technical Control Board (TÜV) Rheinland UK Ltd. 01/205U/5640.01/23
  • German Technical Control Board (TÜV) Rheinland 01/205/5640.01/23
  • UL E331130
  • Storage temperature -25 °C … 55 °C
  • Ambient temperature 0 °C … 50 °C
  • Note on ambient temperature Power must be reduced by 3% per °C at ambient temperatures above 40°C.
  • UL ambient temperature 0 °C … 40 °C
  • Relative air humidity 5 – 90%
  • Non-condensing
    Max. installation height 2000 m
  • Note on max. installation height From 1000 m: power reduction by 1% per 100 m.
  • Degree of protection IP20
  • Protection class I
  • Overvoltage category III
  • Pollution degree 2
  • Immunity to surge 6 kV
  • Note on materials RoHS-compliant
  • LABS (PWIS) conformity VDMA24364 zone III
  • Phases of nominal operating voltage 3-phase
  • Nominal operating voltage AC 400 V
  • Permissible voltage fluctuations +/- 10 %
  • Input voltage range AC 200 V … 480 V
  • Mains frequency 48 Hz … 62 Hz
  • Nominal current, load supply 15 A
  • Peak current load power supply 45 A
  • Active PFC no
  • Mains filter Integrated
  • System voltage to EN 61800-5-1 300 V
  • Max. short circuit current rating of the mains 10 kA
  • Mains types TN
  • IT
  • Nominal voltage load voltage DC 560 V
  • Permissible range for load power supply ± 10 %
  • Max. intermediate circuit voltage DC 800 V
  • Brake resistor, integrated 47 Ohm
  • Pulse power, brake resistance 13.6 kVA
  • Pulse energy for braking resistor 1200 Ws
  • Nominal power braking resistor (IEC) 100 W
  • Brake resistor, external 40 Ohm … 60 Ohm
  • Max. continuous output of the external braking resistor (IEC) 3000 W
  • Nominal voltage for logic power supply DC 24 V
  • Permissible range for logic voltage ± 20 %
  • Current consumption of logic power supply without clamping brake 0.5 A
  • Current consumption for logic supply with parking brake 2 A
  • Max. current consumption, logic power supply with clamping brake and
  • I/O
  • 2.5 A
  • Output voltage class AC 3x (0 – input) V
  • Nominal current per phase, effective 12 A
  • Peak current per phase, effective 36 A
  • Max. peak current duration 2 s
  • Controller nominal output 6000 VA
  • Maximum output 18000 VA
  • Output frequency 0 Hz … 599 Hz
  • Max. length of motor cable without external mains filter 25 m
  • Max. output current of holding brake 1.5 A
  • Max. voltage drop from logic supply to brake output 1 V
  • Number of inputs for motor temperature sensor 1