Dwyer Series 628 INDUSTRIAL PRESSURE TRANSMITTER

View List

Description

Dwyer Series 628 INDUSTRIAL PRESSURE TRANSMITTER

The Series 628 Pressure Transmitters are ideal for OEMs with 1% full scale accuracy sensors. The corrosion resistant 316L stainless steel wetted parts allow the Series 626 and 628 transmitters to measure the pressure in a multitude of processes from hydraulic oils to chemicals. The Series 626 and 628 are available in absolute and gage pressure ranges with a variety of optional outputs, process connections and electrical terminations to allow you to select the right transmitter for your application.

Applications:

  • Compressors
  • Pumping Systems
  • Irrigation System Pressure
  • Industrial Process Monitoring
  • Hydraulic

Features:

  • Robust 316L SS oil filled sensor provides shock and vibration resistance insuring stability in controlling pressure for process applications
  • NEMA 4X rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists
  • A wide range of models and connections that can meet pressure measurement specifications from low to very high

Specifications:

  • Service: Compatible gases and liquids
  • Wetted Materials: Type 316L SS
  • Accuracy: 626: 0.25% FS; 626: 0.20% RSS; 628: 1.0% FS; 628: 0.5% RSS; 626 Absolute Ranges: 0.5% FS; 626 absolute ranges: 0.30% RSS. (Includes linearity, hysteresis, and repeatability.)Temperature Limit: 0 to 200°F (-18 to 93°C)
  • Compensated Temperature Range: 0 to 175°F (-18 to 79°C)
  • Thermal Effect: ±0.02% FS/°F. (includes zero and span)
  • Pressure Limits: See table on catalog page
  • Power Requirements: 10 to 30 VDC (for 4 to 20 mA, 0 to 5, 1 to 5, 1 to 6 VDC outputs); 13 to 30 VDC (for 0 to 10, 2 to 10 VDC outputs); 5 VDC ±0.5
  • VDC (for 0.5 to 4.5 VDC ratio-metric output), 10 to 35 VDC (for 4 to 20 mA with -CB option); 13 to 35 VDC or isolated 16 to 33 VAC (for selectable output with -CB option)
  • Output Signal: 4 to 20 mA, 0 to 5 VDC,1 to 5 VDC, 0 to 10 VDC, or 0.5 to 4.5 VDC, or selectable 0 to 5, 1 to 5, 0 to 10, 2 to 10 VDC for -CB option
  • Response Time: 300 ms
  • Loop Resistance: 0-1000 Ω max. R max = 50 (Vps-10) Ω (4-20 mA output), 5 KΩ min (0-5, 1-5, 0.5-4.5 VDC output), 15 KΩ min (1-6, 0-10, 2-10 VDC output)
  • Stability: 1.0% FS/year (Typ.)
  • Current Consumption: 38 mA maximum (for 4 to 20 mA output); 10 mA maximum (for 0 to 5, 1 to 5, 1 to 6, 0 to 10, 2 to 10, 0.5 to 4.5 VDC output); 140 mA maximum (for all 626/628/629-CH with optional LED)
  • Electrical Connections: Model dependent options: Wire end, Hirschman DIN EN 175801-803-C, Packard, Deutsch, M12
  • Process Connection: Model dependent options: 1/8 ?, 1/4 ?, 1/2 ? male NPT; 1/4 ? female NPT; 1/4 ? male or female BSPT; 1/8 ? or 1/4 ? male BSPP ISO 1179; 1/4 ? female SAE valve depressor
  • Enclosure Rating: NEMA 4X (IP66)
  • Mounting Orientation: Mount in any position
  • Weight:10 oz (283 g)
  • Compliance: CE, Optional: NSF/ANSI 61/372, ANSI/UL 218, ANSI/UL 508, NEPA 20

Additional information

Weight 2 kg
Dimensions 20 × 20 × 20 cm