Flowtronic – IFQ MONITOR

View List
Category: Tags: , Brand:

Description

Features:

  • User friendly interface
  • Wide range of languages available: English, German, French, Russian, etc.
  • 1 x RS485 digital sensor interface for RAVEN-EYE® or BELUGA
  • 1 x analog input 4 … 20 mA for external level
  • 3 x analog output 4 … 20 mA for flow, velocity & level
  • 1 x contact closure output for total flow
  • 1 x normally closed relay output for alarm
  • Logger (optional): 2 Gb flash memory (SD card)
  • 7 position sealed membrane keypad
  • 144×32 pixel white on blue graphical display

Applications:

SEWER/CHANNEL NETWORKS MONITORING

  • Large sewer channels
  • Capacity studies
  • Combined sewer overflow (CSO) studies
  • Inflow & infiltration studies
  • High velocity flows
  • Discharge

WASTEWATER TREATMENT PLANTS

  • Flow to treatment
  • Discharge
  • Plant effluent
  • Storm discharge
  • Process flow control

Specifications:

  • Sensor Interface:
  • 1xRS485 digital sensor interface for velocity sensor
  • 1×4-20 mA analog input for level sensor

Setup & Operation

  • 7 position sealed membrane keypad.

    Configuration of level offset, units, output ranges and language through keypad.

Available units:

  • Flow: l/s, m3/h, m3/s, gpd, gpm, cfm

    Velocity: cm/s, m/s, fps

    Levl: mm, cm, m, inch, feet

    Total flow: l, m3, g, cf

Available languages: EN, DE, FR, SP, etc.

  • RTQ-Log software through direct USB communication (optional)

Display & LED

  • 144×32 pixel white-on-blue graphical display.

    Two lines of text display scrolling between: FLOW, VELOCITY, LEVEL and TOTAL FLOW.

    Internal battery status indication.

    GSM network status indication.

    6 status indication LEDs.

Outputs

  • Three 4-20 mA outputs, max. load 250 ohms.

    Outputs are FLOW, LEVEL and VELOCITY.

Logger (optional)

  • Memory: 2 Gb (13 years of data at one minute logging interval)
  • Memory Type: Flash memory (SD card)
  • Datalog Channels: 18
  • Time-based accuracy: <1s/day
  • Data format available: .tsv

Contact Closure

  • 1x relay/SPST-NO output for TOTAL FLOW.

    1x relay/SPST-NC output for FAULTY alarm based on auto-diagnostic system of RAVEN-EYE.

    Rating: 6A at 30 V DC / 6A at 250 V AC

Transmission (Optional)

  • World-wide Penta-band UMTS/HSPa engine (GPRS or 3G)

    GSM: 850/900/1800/1900 MHz

    UMTS: 800/850/900/2100 MHz

    CSD with up to 14.4 Kbps

  • Data files can be sent directly to a FTP server

    Data format type: .tsv or .csv

Communication (optional)

  • Modbus RTU (slave) over RS485 communication port.

Power Supply

  • DC: 9 to 28 V DC (ATEX min. 10V)

    AC: 85 to 265 V AC, 47 to 63 Hz

Enclosure

  • Dimensions: 257 mm W x 217 mm L x 123.5 mm D

    Weight: 2.25 kg

    Material: ABS plastic

    Protection: IP65, NEMA 4

    Max. humidity: 90% r.H. (non-condensing)

Environmental Conditions

  • Operating temperature range: -25 to +55 deg C

    Storage temperature range: -30 to +65 deg C

Additional information

Weight 0.26 kg