Dwyer SERIES IEFB INSERTION THERMAL ENERGY METER

View List
Category: Tags: , , Brand:

Description

Dwyer SERIES IEFB INSERTION THERMAL ENERGY METER
Field Adjustable, BACnet/Modbus® Outputs

The Series IEFB is a field-adjustable insertion thermal energy meter that uses electromagnetic technology to accurately and reliably measure fluid velocity and energy consumption. The high accuracy IEFB is adjustable to fit pipe sizes from 4 to 10″ (100 to 250 mm), while the standard accuracy IEFB fits pipe sizes 4 to 36″ (100 to 900 mm). The IEFB incorporates a temperature meter and a calculator into a single unit. The LCD display provides clear readings of the meter’s values, including temperature and energy consumption, making it ideal for installation on chillers, boilers, and other heating and cooling applications. The high measuring accuracy and long lifetime keeps annual operating costs at a minimum. In addition, it offers several output options, including selectable BACnet MS/TP or Modbus® RTU communications protocol over 2-wire RS-485 and standard analog, frequency, and alarm outputs.

Features:

  • Save time and reduce installation costs with flow, temperature sensors and calculator delivered in one preprogrammed, complete package.
  • Maintain system energy efficiency with high performance accuracy that is maintained through changes in temperature, density or viscosity per universally accepted standard
  • Meet application requirements with field configurable setup displays (-LCD integral option or remote accessory A-IEF-DSP), which accommodate a variety of application configurations with one model through multiple display configurations i.e. pipe size, pipe material, liquid type, analog output, pulse/frequency output, alarm outputs, communication outputs, damping, and calibration factor
  • Quick and easy ordering and set up with Setup Wizard and installation tool that are simple to use and allow for precise installation
    Save time with accessory setup kit A-IEF-KIT that ensures exact installation application depth with included thickness gage and measuring tape
  • Reduced costs, long product life, and minimal maintenance requirements with no moving parts to wear or break and electrodes that discourage fouling
  • Minimize installation costs with isolation valve accessory options to allow for installation in operational systems via hot-tap kit or easy removal without system downtime
  • Required documents included with NIST traceable pass/fail verification certificate included standard for Carbon Steel Schedule 40 pipes sized 4″ (102 mm), 6″ (150 mm), 8″ (200 mm)

Applications:

  • Monitoring chiller cooling output performance
  • Industrial boiler heating performance
  • Energy efficiency monitoringOptimization of heat energy performance
  • Commercial and residential heat energy consumption and metering
  • District heating and cooling monitoringEnergy cost allocation monitoring

Specifications:

  • Service: Compatible clean or dirty non coating, conductive liquids
  • Range: 0 to 20 ft/s (0 to 6 m/s). *For max flowrates >10 ft/s (3 m/s) order option -CC
  • Wetted Materials: Body shaft/fitting: 316 SS; Electrodes: 316 SS; Electrode cap: Polymer/polystyrene; O-ring: Silicone; Thermowells: 304 SS.BTU
  • Accuracy: Per EN1434/ASTM E3137/CSA C900.1-13: High Accuracy Units: Class 2 for 2 to 20 ft/s (0.6 to 6 m/s)**; Standard Accuracy Units: Class 3 for 6.5 to 20 ft/s (2 to 6 m/s)**. **Verified at standard temperature 73.4°F (23°C) refer to listed standards for detailed accuracy formulations
  • Flow Sensor Accuracy: High Accuracy Units: ±0.5% of reading at calibrated velocity, ±1% of reading from 2 to 20 ft/s (0.6 to 6 m/s) ±0.02 ft/s (±0.006 m/s) at < 2 ft/s (0.6 m/s); Standard Accuracy Units: ±1% FS
  • Temperature Accuracy: Class B ±(0.30 + 0.005*t)°C per EN60751.Differential Temperature Accuracy: Et = ±[0.5 +3*(Delta)(Theta)min/(Delta)(Theta)] % per EN1434 for differential temperature
  • Calculator Accuracy: Ec = ±[0.5 +(Delta)(Theta)min/(Delta)(Theta)] % per EN1434
  • Temperature Compensation: 140 to 220°F (60 to 104.4°C) < 2% error over ±30°F (-1.1 °C) change, 40 to 70°F (4.4 to 21.1°C) < 2% error over ±10°F (-12.2°C) change
  • Temperature Limits: Ambient: -20 to 160°F (-29 to 71°C)**; LCD -4 to 158°F (-20 to 70°C); Process: 15 to 250°F (-9 to 121°C); Storage: -40 to 185°F (-40 to 85°C)
  • Process Connection: Flowmeter: 1″ NPT or BSPT with accessory full port ball valve options; Thermowell: (2) 1/2″ NPT or BSPT thermowell with 1″ full port ball valve options
  • Pressure Limit: 400 psi (27.6 bar) @ 100°F (37.8°C)
  • Pressure Drop: < 0.1 psi at 12 ft/s in 4″ (<0.01 bar at 3.7 m/s in 100 mm) and larger pipe
  • Outputs: (1) Analog: 4-20 mA, 0-5 V, 0-10 V or 2-10 V (display selectable); (1) Pulse/Frequency: 0-15 V peak pulse, 0 to 500 Hz or scalable pulse output (display selectable); (2) Alarm: Empty pipe detection or minimum/maximum velocity, (display selectable) & Reverse flow output indication
  • Power Requirements: 12-42 VDC, .25 A @ 24 VDC; 12-36 VAC
  • Electrical Connection: Removable terminal blocks, (2) model selectable 1/2″ female NPT conduit connection, (2) PG 16 gland or (2) PG 16 gland with 10 ft (3 m) 9 conductor 22 AWG plenum rated cables, accessory cable lengths up to 200 ft (61 m) optional
  • Display: (-LCD option): 2 x 2″ (50 x 50 mm) graphic LCD with backlight
  • Conductivity: >20 microsiemens
  • Enclosure Material: Powder coated die cast aluminum
  • Enclosure Ratings: NEMA 6P (IP68) (Non display models); NEMA 4X (IP66) (-LCD option)
  • Agency Approvals:BTL.

COMMUNICATIONS (-COM OPTION)

  • Type: BACnet MS/TP or Modbus® RTU communication protocol (default disabled, display selectable)
  • Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, or 115200 bps (display selectable)
  • Device Load:1/8 unit load.

ADDITIONAL SPECIFICATIONS

  • Applicable Pipe Material: Most popular plastic and metal pipes; i.e. Carbon steel, SS, copper, UPVC/PVDF, galvanized steel, mild steel, and brass
  • Applicable Pipe Size: 4 to 36″ (100 to 900 mm), model dependent. See model chart
  • Diameter Length Requirements: >10 upstream, >5 downstream
  • Temperature Resistance: Matched 4 wire platinum RTD’s
  • Relative Humidity: 10 to 90% non-condensing
  • Output Impedance: 4 to 20 mA: 536 Ω; 5V: 500 Ω 10V: 1.27k Ω.

Models:

  • IEFB-FB-PG-T10-LCD Insertion Electromagnetic energy system with LCD display, 4″ (100 MM) pipe, 1% of reading, BSPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors
  • IEFB-FB-PGR10LCDCOM Insertion Electromagnetic energy system with LCD display, 4″ (100 MM) pipe, 1% of reading, BSPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells, BACnet/Modbus® communication output
  • IEFB-FN-CNDR10LCDCOM Insertion Electromagnetic energy system with LCD display, 8″ (200 MM) pipe, 1% of reading, NPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells, BACnet/Modbus® communication output
  • IEFB-HB-PG-R10-LCD Insertion Electromagnetic energy system with LCD display, high accuracy 4-10″ (100-250 MM) pipe; 1% of reading, 1″ Male BSPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells
  • IEFB-HB-PG-T10-LCD Insertion Electromagnetic energy system with LCD display, high accuracy 4-10″ (100-250 MM) pipe; 1% of reading, 1″ Male BSPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors
  • IEFB-HB-PGR10LCDCOM Insertion Electromagnetic energy system with LCD display, high accuracy 4-10″ (100-250 MM) pipe; 1% of reading, 1″ Male BSPT process connections, PG 16 gland, (2) 10´ (3 M) PT temperature sensors with hot-tap thermowells, BACnet/Modbus® communication output
  • IEFB-HB-PGT10LCDCOM Insertion Electromagnetic energy system with LCD display, high accuracy 4-10″ (100-250 MM) pipe; 1% of reading, 1″ Male BSPT process connections, PG 16 gland, (2) 10´ (3 M) PT temperature sensors, BACnet/Modbus® communication output
  • IEFB-HN-CND-R10-LCD Insertion Electromagnetic energy system with LCD display, high accuracy 4 to 10″ (100-250 MM) pipe, 1% of reading, 1″ male NPT process connection, NPT process connections, conduit connections, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells
  • IEFB-HN-CND-T10-LCD Insertion Electromagnetic energy system with LCD display, high accuracy 4 to 10″ (100-250 MM) pipe, 1% of reading, 1″ male NPT process connection, NPT process connections, conduit connection, (2) 10′ (3 M) PT temperature sensors
  • IEFB-HN-CNDR10LCDCOM Insertion Electromagnetic energy system with LCD display, high accuracy 4 to 10″ (100-250 MM) pipe, 1% of reading, 1″ male NPT process connection, NPT process connections, conduit connection, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells, BACnet/Modbus® communication output
  • IEFB-HN-CNDT10LCDCOM Insertion Electromagnetic energy system with LCD display, high accuracy 4-10″ (100-250 MM) pipe, 1% of reading, 1″ male NPT process connection, NPT process connections, conduit connection, (2) 10′ (3 M) PT temperature sensors, BACnet/Modbus® communication output
  • IEFB-IB-PG-T10-LCD Insertion Electromagnetic energy system with LCD display, 6″ (150 MM) pipe, 1% of reading, BSPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors
  • IEFB-IB-PGR10LCDCOM Insertion Electromagnetic energy system with LCD display, 6″ (150 MM) pipe, 1% of reading, BSPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells, BACnet/Modbus® communication output
  • IEFB-IN-CNDR10LCDCOM Insertion Electromagnetic energy system with LCD display, 6″ (150 MM) pipe, 1% of reading, NPT process connections, PG 16 gland, (2) 10′ (3 M) PT temperature sensors with hot-tap thermowells, BACnet/Modbus® communication output
  • IEFB-LB-PGR10LCDCOM Insertion Electromagnetic energy system with display, 4″-<10″ (100-<250MM) pipe, 1% FS, BSPT process connections, PG 16 gland, BACnet/Modbus® communication output
  • IEFB-LN-CND-R10-LCD Insertion Electromagnetic energy system with display, 4″-<10″ (100-<250MM) pipe, 1% FS, NPT process connections, conduit connection
  • IEFB-LN-CNDR10LCDCOM Insertion Electromagnetic energy system with display, 4″-<10″ (100-<250MM) pipe, 1% FS, NPT process connections, conduit connection, BACnet/Modbus® communication output
  • IEFB-SB-PGR10LCDCOM Insertion Electromagnetic energy system with display, 4″-36″ (100-900 MM) pipe, 1% FS, BSPT process connections, PG 16 gland, BACnet/Modbus® communication output
  • IEFB-SN-CNDR10LCDCOM Insertion Electromagnetic energy system with display, 4″-36″ (100-900 MM) pipe, 1% FS, NPT process connections, conduit connection, BACnet/Modbus® communication output