Dwyer SERIES CMT200 CARBON MONOXIDE TRANSMITTER

View List

Description

Dwyer SERIES CMT200 CARBON MONOXIDE TRANSMITTER
Current/Voltage Selectable Output, 200 PPM Range

The Series CMT200 Carbon Monoxide Transmitter provides a field selectable current or voltage output that is proportional to the gas concentration in underground parking garages, vehicle maintenance facilities, or mechanical rooms. A field replaceable, electrochemical sensor provides accurate readings for up to 4 years with proper calibration. Field calibration can be done by using Model GCK-200CO-2000CO2 calibration gas, Model A-507A calibration adapter, and the on board span and zero potentiometers.

Features:

  • Field selectable current or voltage outputs
  • Replaceable sensor
  • Field calibration kits

Applications:

  • Garage ventilation
  • Mechanical room monitoring

Specifications:

  • Sensor: Field replaceable electrochemical, 4 year typical lifespan
  • Range: 0 to 200 ppm
  • Coverage Area: 5000 to 7000 sq. ft. typical.
  • Accuracy: ±2% FS at the time of calibration
  • Output Drift: <5% per year in air
  • Temperature Limits: -4 to 122°F (-20 to 50°C)
  • Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C)
  • Humidity Limits: 15 to 90% RH constant; 0 to 99% RH intermittent
  • Response Time: <45 s. to 90% of final value
  • Calibration: 15 turn span and zero adjustment potentiometers
  • Housing: UV resistant polycarbonate
  • Output: Jumper selectable 4 to 20 mA (loop powered) or 2 to 10 V (load must be >50 kΩ)
  • Power Requirements: Current Output: 18 to 28 VDC;
  • Voltage Output: 18 to 28 VDC/VAC, reverse polarity protected
  • Electrical Connection: Removable terminal block, includes two PG11 and one PG 16 knockouts for conduit fitting
  • Weight: 0.28 lb (0.11 kg)
  • Agency Approvals: CE

Models:

  • CMT200 Carbon Monoxide Transmitter, 0 to 200 PPM CO, 4 to 20 mA/2 to 10 VDC outputs.
  • CMT200-FC Carbon monoxide transmitter, 0-200 PPM CO, 4-20 mA/2-10 VDC outputs, includes factory calibration certificate
  • CMT200-R Carbon Monoxide Transmitter, 0 to 200 PPM CO, 4 to 20 mA/2 to 10 VDC outputs, rectangular enclosure
  • CMT200-R-FC Carbon monoxide transmitter, 0-200 PPM CO, 4-20 mA/2-10 VDC outputs, rectangular enclosure, includes factory calibration certificate