Description
Festo Pressure sensor SPAN-B2R-G18M-PNLK-PNVBA-L1
- Symbol: 00995685
- Approval: RCM trademark
- c UL us listed (OL)
- CE mark (see declaration of conformity): To EU EMC Directive
- In accordance with EU RoHS Directive
- CE marking (see declaration of conformity): To UK instructions for EMC
- To UK RoHS instructions
- Certificate issuing authority: UL E322346
- Note on materials: RoHS-compliant
- Measured variable: Relative pressure
- Measurement method: Piezoresistive pressure sensor
- Start value for pressure measuring range: -0.1 MPa
- Start value for pressure measuring range: -1 bar
- Start value for pressure measuring range: -14.5 psi
- End value for pressure measuring range: 0.1 MPa
- End value for pressure measuring range: 1 bar
- End value for pressure measuring range: 14.5 psi
- Max. overload pressure: 5 bar
- Overload pressure: 0.5 MPa
- Overload pressure: 5 bar
- Overload pressure: 72.5 psi
- Operating medium: Compressed air to ISO 8573-1:2010 [7:4:4]
- Inert gases
- Note on operating and pilot medium: Lubricated operation possible
- Media temperature: 0 °C … 50 °C
- Ambient temperature: 0 °C … 50 °C
- Accuracy in ± % FS: 1.5 %FS
- Repetition accuracy in ± %FS: 0.3 %FS
- Temperature coefficient in ± %FS/K 0.05 %FS/K
- Switching output: 2 x PNP or 2 x NPN, switchable
- Switching function: Window comparator
- Threshold value comparator
- Auto difference monitoring
- Switching element function: N/C or N/O contact, switchable
- Max. output current: 100 mA
- Analogue output: 0 – 10 V
- 4 – 20 mA
- 1 – 5 V
- Max. load resistance current output: 500 Ohm
- Min. load resistance voltage output: 20 kOhm
- Short circuit current rating: yes
- Protocol: IO-Link®
- IO-Link, Protocol version: Device V 1.1
- IO-Link, Profile: Smart sensor profile
- IO-Link, Function classes: Binary data channel (BDC)
- Process data variable (PDV)
- Identification
- Diagnostics
- Teach channel
- IO-Link, communication mode: COM2 (38.4 kBaud)
- IO-Link, SIO-Mode support: Yes
- IO-Link, Port class: A
- IO-Link, Process data length OUT: 0 bytes
- IO-Link, Process data length IN: 2 bytes
- IO-Link, Process data content IN: 14 bit PDV (pressure measurement value)
- 2 bit BDC (pressure monitoring)
- IO-Link, Min. cycle time: 3 ms
- IO-Link, Data storage required: 500 Byte
- Operational voltage range DC: 15 V … 30 V
- Reverse polarity protection: For all electrical connections
- Electrical connection 1, connection type: Plugs
- Electrical connection 1, connector system :Connection pattern L1J
- Electrical connection 1, number of connections/cores: 4
- Electrical connection 1, connection pattern: 00995428
- Type of mounting: Front panel mounting
- Via thread
- Via wall/surface bracket
- Mounting position: optional
- Pneumatic connection Male: thread G1/8
- Female thread: M5
- Product weight: 46 g
- Material housing: PA-reinforced
- Material in contact with the medium: FPM
- High-alloy stainless steel
- Display type: Illuminated LCD
- Displayable units: MPa
- bar
- inH2O
- inHg
- kPa
- kgf/cm²
- mbar
- mmHg
- psi
- Setting options:IO-Link®
- Teach-in
- Via display and keys
- Protection against tampering IO-Link
- PIN code
- Setting range threshold value: 0 % … 100 %
- Setting range hysteresis: 0 % … 90 %
- Degree of protection: IP40
- Corrosion resistance class CRC: 2 – Moderate corrosion stress
- LABS (PWIS) conformity: VDMA24364-B1/B2-L
- Suitability for the production of Li-ion batteries: Metals with more than 1% copper, zinc or nickel by mass are excluded
- from use. Exceptions are nickel in steel, chemically nickel-plated
- surfaces, printed circuit boards, cables, electrical plug connectors and coils
- Cleanroom class: Class 4 according to ISO 14644-1