Festo Pressure sensor SPAN-B2R-G18M-PNLK-PNVBA-L1

View List

Description

Festo Pressure sensor SPAN-B2R-G18M-PNLK-PNVBA-L1

  • Symbol: 00995685
  • Approval: RCM trademark
  • c UL us listed (OL)
  • CE mark (see declaration of conformity): To EU EMC Directive
  • In accordance with EU RoHS Directive
  • CE marking (see declaration of conformity): To UK instructions for EMC
  • To UK RoHS instructions
  • Certificate issuing authority: UL E322346
  • Note on materials: RoHS-compliant
  • Measured variable: Relative pressure
  • Measurement method: Piezoresistive pressure sensor
  • Start value for pressure measuring range: -0.1 MPa
  • Start value for pressure measuring range: -1 bar
  • Start value for pressure measuring range: -14.5 psi
  • End value for pressure measuring range: 0.1 MPa
  • End value for pressure measuring range: 1 bar
  • End value for pressure measuring range: 14.5 psi
  • Max. overload pressure: 5 bar
  • Overload pressure: 0.5 MPa
  • Overload pressure: 5 bar
  • Overload pressure: 72.5 psi
  • Operating medium: Compressed air to ISO 8573-1:2010 [7:4:4]
  • Inert gases
  • Note on operating and pilot medium: Lubricated operation possible
  • Media temperature: 0 °C … 50 °C
  • Ambient temperature: 0 °C … 50 °C
  • Accuracy in ± % FS: 1.5 %FS
  • Repetition accuracy in ± %FS: 0.3 %FS
  • Temperature coefficient in ± %FS/K 0.05 %FS/K
  • Switching output: 2 x PNP or 2 x NPN, switchable
  • Switching function: Window comparator
  • Threshold value comparator
  • Auto difference monitoring
  • Switching element function: N/C or N/O contact, switchable
  • Max. output current: 100 mA
  • Analogue output: 0 – 10 V
  • 4 – 20 mA
  • 1 – 5 V
  • Max. load resistance current output: 500 Ohm
  • Min. load resistance voltage output: 20 kOhm
  • Short circuit current rating: yes
  • Protocol: IO-Link®
  • IO-Link, Protocol version: Device V 1.1
  • IO-Link, Profile: Smart sensor profile
  • IO-Link, Function classes: Binary data channel (BDC)
  • Process data variable (PDV)
  • Identification
  • Diagnostics
  • Teach channel
  • IO-Link, communication mode: COM2 (38.4 kBaud)
  • IO-Link, SIO-Mode support: Yes
  • IO-Link, Port class: A
  • IO-Link, Process data length OUT: 0 bytes
  • IO-Link, Process data length IN: 2 bytes
  • IO-Link, Process data content IN: 14 bit PDV (pressure measurement value)
  • 2 bit BDC (pressure monitoring)
  • IO-Link, Min. cycle time: 3 ms
  • IO-Link, Data storage required: 500 Byte
  • Operational voltage range DC: 15 V … 30 V
  • Reverse polarity protection: For all electrical connections
  • Electrical connection 1, connection type: Plugs
  • Electrical connection 1, connector system :Connection pattern L1J
  • Electrical connection 1, number of connections/cores: 4
  • Electrical connection 1, connection pattern: 00995428
  • Type of mounting: Front panel mounting
  • Via thread
  • Via wall/surface bracket
  • Mounting position: optional
  • Pneumatic connection Male: thread G1/8
  • Female thread: M5
  • Product weight: 46 g
  • Material housing: PA-reinforced
  • Material in contact with the medium: FPM
  • High-alloy stainless steel
  • Display type: Illuminated LCD
  • Displayable units: MPa
  • bar
  • inH2O
  • inHg
  • kPa
  • kgf/cm²
  • mbar
  • mmHg
  • psi
  • Setting options:IO-Link®
  • Teach-in
  • Via display and keys
  • Protection against tampering IO-Link
  • PIN code
  • Setting range threshold value: 0 % … 100 %
  • Setting range hysteresis: 0 % … 90 %
  • Degree of protection: IP40
  • Corrosion resistance class CRC: 2 – Moderate corrosion stress
  • LABS (PWIS) conformity: VDMA24364-B1/B2-L
  • Suitability for the production of Li-ion batteries: Metals with more than 1% copper, zinc or nickel by mass are excluded
  • from use. Exceptions are nickel in steel, chemically nickel-plated
  • surfaces, printed circuit boards, cables, electrical plug connectors and coils
  • Cleanroom class: Class 4 according to ISO 14644-1